B.2.2 Mounting the NCS
Function
The positioner facilitates the separate installation of the position detection system. The stroke
or rotary angle is measured directly at the actuator by means of a non-contacting sensor. It is
therefore possible to install the controller unit at some distance away, e.g. on a mounting pipe
or similar. The positioner is connected to the position detection system by means of an
electrical cable.
Such a separate installation is useful whenever the ambient conditions at the valve exceed the
specified positioner values.
The NCS consists of a molded sensor for fixed installation and a magnet. The magnet is
mounted to the spindle on linear actuators, or to the stub shaft on part-turn actuators. The
sensor housing is mounted onto the console on part-turn actuators and to the bracket on linear
actuators. The bracket can be a NAMUR type, or any other mounting bracket.
Auxiliary power is supplied to the NCS via the Analog Input Module (AIM) 6DR4004-6F and
EMC compatibility is ensured at the same time.
You have the following options:
To order the Analog Input Module (AIM) already installed in the positioner, Catalog FI 01
To retrofit the Analog Input Module (AIM) in the positioner; article number 6DR4004-6F. For
information on retrofitting the Analog Input Module (AIM), refer to the Installing/mounting
(Page 37) section of the positioner operating instructions.
Pneumatic line
Pneumatic line for double-action actuators
Position detection system (10 kΩ potentiometer or NCS)
Electrical cable
Retrofittable Analog Input Module (AIM) (in the positioner)
Positioner
Figure B-3 Separate installation of the NCS and positioner
External position detection
B.2 Non-Contacting Sensor
SIPART PS2 with 4 to 20 mA/HART
Operating Instructions, 11/2019, A5E00074631-AE 273

Table of Contents

Other manuals for Siemens SIPART PS2 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPART PS2 series and is the answer not in the manual?

Siemens SIPART PS2 series Specifications

General IconGeneral
BrandSiemens
ModelSIPART PS2 series
CategoryValve Positioners
LanguageEnglish

Related product manuals