SNMP and Remote Access SWT 3000 Equipment Manual
Page - 10 Edition p3_3_2x 08/09 © SIEMENS AG 2008
• RS232 tunnel
RAS function of the server for direct connection of the PowerSys program via
TCP/IP. This function blocks the SNMP function and is indicated with the trap “Pow-
erSys session active”.
• Config.
Configuration data base of SNMP server.
• Port1
RS232 interface1 for the communication between the SNMP server and the
SWT 3000 device.
Polling of the SWT 3000 Device data
The SNMP server generates during the start up procedure an image of all configuration parame-
ter and polls cyclic the status information of the connected SWT 3000 device according MIB. The
configuration parameter are refreshed after new start of the SNMP server resp. after recovering of
an interrupted serial connection to the SWT 3000. The data of the SWT3000 event recorder are
read only after request from the NMS.
SWT 3000 read general information
The following information can be read:
• SWT 3000 hardware information
PU3 hardware release, DLE hardware release, IFC1 hardware release, IFC2 hard-
ware release
• SWT 3000 counter (max. 24 inputs, max. outputs)
Input number and counter value, output number and counter value
• SWT 3000 Event recorder
Recorder sequence number, time stamp, event group and event number, event de-
scription
SWT 3000 read hardware configuration
The following hardware configuration can be read:
• System configuration
Operation mode, purpose, VF variant, analog interface, digital interface. primary
path, secondary path, Tx / Rx address, coded transmission, permissive or direct trip-
ping, IFC1/2 type
• RM configuration
RM address, master, slave
SWT 3000 set commands
The following commands can be set from the NMS:
Reset device, SWT line select, LID local loop, LID remote loop