SWT 3000 Equipment Manual SNMP and Remote Access
© SIEMENS AG 2008 Edition p3_3_2x 08/09 Page - 19
Setting options
Table 4: Setting options for the SNMP operating configuration
Parameter Access Range of values Default
DHCP read/write enabled/disabled disabled
IP-Address read/write xxx.xxx.xxx.xxx 192.168.3.127
Subnet-Mask read/write xxx.xxx.xxx.xxx 255.255.255.0
Gateway Address read/write xxx.xxx.xxx.xxx 0.0.0.0
Local-Port (RAS) read/write 10000 - 10100 10001
Product-Id read String MLFB 7VR 9246
Firmware-Version read String Vxx.xx
MAC Address read String xx-xx-xx-xx-xx-xx
Config.-Password write String private (max. 10 characters)
IP –Address
Subnet-Mask have to be set according the customers network
Gateway Address
DHCP
Local Port (RAS)
The address is used for remote access with the service program PowerSys
Config Password
The config. password is requested for the web login and can be changed.
Trap destination configuration
The NMS addresses as well as the community string for set /get has to be adjusted via web
login and must match between the SNMP server and the NMS.
The min active time adjustable between 0 – 3000 sec, is the minimum time the alarm has to be
active before a rising trap is sent.
The fall down delay adjustable between 0 – 3000 sec, is the min time the alarm has to be inac-
tive before a falling trap is sent. Both adjustments are used to prevent a sequence of events in
case of cyclic alarm indications.
NMS commissioning
The necessary MIBs are available on the PowerSys CD provided with the PowerLink system.
They have to be integrated in the NMS. After the NMS has been configured, traps from the SNMP
server are received. It is also possible to read PowerLink (ref. to page 10) resp. iSWT information
(ref. to page Fehler! Textmarke nicht definiert.) or configuration (ref. to page 10). Commands can
be set as well from the NMS (ref. to page 10).
Access to the PowerLink via the SNMP server is also possible with the PowerSys service pro-
gram. In this case the connection to the NMS is interrupted. A corresponding trap is sent from the
SNMP server.
Network time protocol NTP
Activation of the NTP (NTP synchronization ;) offers the possibility to synchronize the timer of
the iSWT with the network time protocol.
The NTP server is the PC in the network providing the time. Enter either the IP address or the
internet address.
The Time zone is always the GMT. Please select the local deviation (±12h).
The Poll interval describes how often the time is read from the NTP server.