ABB | SACE Emax 2
Mechanical accessories | 5 - Operating mode for E1.2279 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. A
Circuit breaker racking-in/
racking-out operations
The following is the procedure for the insertion of the moving part in the fixed part:
WARNING!
Make sure the circuit-breaker is disconnected from all sources of energy.
Switch the circuit-breaker to the open position with springs discharged.
WARNING! Before proceeding, remove all equipment used during the work and remove
processing waste and materials used.
1. Make sure that signalling device on the fixed part indicates the DISCONNECT position. See Figure
79.
Figure 79
2. Position the moving part in the fixed part and push until it comes to a stop. See Figure 80 and Figure
81.
Figure 80
Figure 81
3. Extract the disconnection crank from its housing See Figure 82.
4. Press the lock pushbutton and insert the crank in the moving part. In this phase the moving part is still
in DISCONNECT position. See Figure 83.
Figure 82
2
1
Figure 83
Continued on the next page

Table of Contents

Other manuals for ABB SACE Emax E2.2

Question and Answer IconNeed help?

Do you have a question about the ABB SACE Emax E2.2 and is the answer not in the manual?

ABB SACE Emax E2.2 Specifications

General IconGeneral
Rated Voltage (Ue)Up to 690V AC
StandardsIEC 60947-2
Poles3, 4
TypeAir Circuit Breaker
Protection FunctionsOverload, Short-circuit
MountingFixed
DimensionsVarious, depending on frame size and configuration. Consult ABB documentation.
WeightVarious, depending on frame size and configuration. Consult ABB documentation.

Summary

Circuit-breakers E1.2-E2.2-E4.2-E6.2

3 - Standards

Details compliance with international standards like IEC 60947 and EC directives.

Guide to the product choice

1 - List for Emax 2 selection

Provides criteria for selecting Emax 2 circuit-breakers based on device, standard, and characteristics.

Electrical characteristics

Lists electrical specifications such as rated voltage, current, and short-circuit breaking capacity.

Protection functions of the electronic trip units

Outlines available basic and additional protection functions for trip units.

Electrical and mechanical accessories

Lists electrical signalling, service trip units, motor operators, and mechanical accessories.

2 - Selectivity between ABB SACE circuit-breakers

Explains how to achieve selectivity between ABB SACE circuit-breakers for fault isolation.

Documents and Tools for the design engineer

2 - Software list

Lists available software tools for Emax 2 design, estimation, and thermal calculation.

3 - Documentation list

Provides a list of available brochures, product notes, white papers, catalogues, and handbooks.

Introduction to Ekip trip units

1 - Presentation

Introduces the five types of protection trip units for SACE Emax 2 and their functionalities.

Integrated functions: Self-diagnosis, Test and Power Controller

Explains integrated functions like self-diagnosis, testing, and power control.

Ekip Dip protection trip unit

1 - Operator interface

Describes the operator interface components and LEDs for Ekip Dip trip units.

2 - Protections

Details protections like L, S, I, G, and their parameters for Ekip Dip.

4 - Test

Guides through performing LED tests, battery tests, protection tests, and opening tests.

6 - Ekip Dip: additional functions

Describes functions like Maintenance, Local Bus, Date/Time, Programmable States, and Functions.

Ekip Touch protection trip unit

1 - Layout of the interface

Describes the functions, components, and navigation of the Ekip Touch interface.

6 - Menu

Provides access to Protections, Advanced, Settings, Test, About, and Measurements menus.

8 - Setting the parameters

Guides on modifying parameters, programming trip units, and editing pages.

9 - Touch protections

Introduces touch protections and lists protections against overload, short circuit, and earth faults.

10 - Measuring Pro protections

Details protections like UV, OV, VU, UF, OF, RP, Phase Sequence, Cos φ, and Synchrocheck.

11 - Hi-Touch protections

Introduces Hi-Touch protections and lists protections like S2, D, UV2, OV2, UF2, OF2.

12 - G Touch protections

Introduces G Touch protections and lists protections like S(V), RV, RQ, OQ, OP, UP.

13 - G Hi-Touch protections

Introduces G Hi-Touch protections and lists protections like ROCOF, S2(V), RQ2.

14 - External toroid protections

Explains Gext and Rc protections and their operating principles.

15 - Touch measurements

Lists available measurements for trip units, including instantaneous currents and history.

16 - Ekip Measuring Measurements

Details measurements for voltage, power, frequency, and energy using Ekip Measuring modules.

17 - Hi-Touch measurements

Covers Hi-Touch measurements for waveforms, harmonics, and network analysis.

18 - Test

Guides on performing Autotest, Trip Test, Test CB, Zone Selectivity, Ekip Signalling, and Rc Test.

19 - Self-diagnosis

Explains alarm tests, self-diagnosis signals, and programming errors.

20 - Operating features

Details operating currents, voltages, and auxiliary power supply specifications.

21 - Additional Ekip Touch functions

Covers functions like Line frequency, Local/Remote, Local Bus, Harmonics, Power Controller, etc.

22 - Default parameters

Lists default parameters for Ekip Touch, Hi-Touch, and G Hi-Touch trip units.

23 - Ekip Power Controller

Explains the Ekip Power Controller function for load management and energy optimization.

Protection curves

1 - Introduction

Illustrates trip curves for available protections and trip units.

2 - DIP protections

Shows tripping curves for L-I, L-S(t=k/I^2)-I, L-S(t=k)-I, and G protections.

3 - Touch protections

Displays tripping curves for L-I, L-S(t=k/I^2)-I, and L-S(t=k)-I protections.

4 - Measuring Pro protections

Shows tripping curves for UV, OV, VU, UF, OF, and RP protections.

5 - Hi-Touch protections

Displays tripping curves for D protection.

6 - G Touch protections

Shows tripping curves for S(V), RV, RQ, OQ, OP, and UP protections.

7 - G Hi-Touch protections

Displays tripping curves for ROCOF protection.

8 - External toroid protections

Shows tripping curves for Rc protection.

System Interface

Documents

Lists documents for Ekip Com communication modules and their integration files.

Specific applications

1 - Zone Selectivity

Explains Zone Selectivity, its implementation, and logic/hardware selectivity.

2 - Load control

Details the Ekip Power Controller for load management, power limits, and energy optimization.

3 - Generator protection

Describes specific protections and functions for low voltage synchronous generators.

Accessories

1 - Preliminary considerations

Covers standard accessories for fixed and withdrawable circuit-breakers.

2 - Wiring diagrams

Provides general wiring diagrams for circuit-breakers and switch-disconnectors.

Circuit-breaker terminal box

Shows terminal box views and differences for E1.2 and E2.2-E6.2 circuit-breakers.

Disassembly operations for circuit breakers E1.2

Details steps for removing front cover and protections for E1.2 circuit-breakers.

Mechanical Interlocks

Explains four types of mechanical interlocks for controlling circuit-breaker logic.

Operating modes for E2.2-E4.2-E6.2

Provides step-by-step instructions for manual opening and closing operations.

6 - Environmental conditions

Covers installation environment, temperature, weather, dust, and vibration standards.

7 - Installation

Provides information on overall dimensions and mounting hole drilling.

8 - Technical characteristics

Details protection degrees, dissipated power, and derating due to temperature.

9 - Accessories

Lists standard and additional accessories for circuit-breakers.

Identification of alarms or failures

Guides on identifying faults, causes, remedies, and signals shown on the display.

LEAP analysis program

Introduces the LEAP analysis program for assessing circuit-breaker health and life expectancy.

Service

Describes ABB's PowerCare services for electrification systems.

Related product manuals