Ekip Touch protection trip unit | 9 - Touch protections73 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. A
Summary table of basic protections
ABB
ANSI
(1)
Threshold
Threshold
tolerance
(3)
Time
Calculation
formula t
t
(2)
Calculation
example t
t
(2)
Tolerance t
t
(3)
L
(60947-2)
49
I1 = 0.4…1 In
step = 0.001 In
Activation for If in the
range (1.05...1.2) x I1
t1 = 3…144 s
step = 1 s
t
t
= (9 t1) / (If
/ I1)
2
t
t
= 6.75 s with:
I1 = 0.4 In; t1 = 3 s;
If = 0.8 In
± 10 % with If
6 In
± 20 % with If >
6 In
L
(60255-151)
(9)
49
I1 = 0.4…1 In
step = 0.001 In
Activation for If in the
range (1.05...1.2) x I1
t1 = 3…144 s
step = 1 s
t
t
= (t1 x a x b)
/ ((If / I1)
k
-1)
See the table below
± 10 % with If
6 In
± 20 % with If >
6 In
S
(t = k)
50 TD
I2 = 0.6...10 In
step = 0.1 In
± 7 % with If 6 In
± 10 % with If > 6 In
t2 = 0.05…0.8 s
step = 0.01 s
t
t
= t2 -
The better of the
two values:
± 10 % or ± 40
ms
S
(t = k / I
2
)
51
I2 = 0.6...10 In
step = 0.1 In
± 7 % with If 6 In
± 10 % with If > 6 In
t2 = 0.05…0.8 s
step = 0.01 s
t
t
=
(100 t2) / (If)
2
t
t
= 5 s con:
I2 = 1 In; t2 = 0.8 s;
If = 4 In
± 15 % with If
6 In
± 20 % with If >
6 In
I 50
I3 = 1.5...15 In
step = 0.1 In
± 10 % Not adjustable t
t
30 ms - -
G
(t = k)
50N TD
I4
(4)
= 0.1...1 In
step = 0.001 In
± 7 %
t4 =
Instantaneous…1 s,
0.1...1s
step = 0.05 s
t
t
= t4 -
The better of the
two values:
± 10 % or ± 40
ms
(8)
G
(t = k / I
2
)
51N
I4
(4)
= 0.1...1 In
step = 0.001 In
± 7 %
t4 = 0.1…1 s
step = 0.05 s
t
t
=
2 / (If / I4)
2
t
t
= 0.32 s with:
I4 = 0.8 In; t4 = 0.2
s; If = 2 In
± 15 %
2I 50
I31 = 1.5...15 In
step = 0.1 In
± 10 % Not adjustable t
t
30 ms - -
MCR -
I3 = 1.5...15 In
step = 0.1 In
± 10 %
40…500 ms
(5)
step = 0.01 s
t
t
30 ms - -
IU 46
I6 = 2…90 %
step = 1 %
± 10 %
t6 = 0.5…60 s
step = 0.5 s
t
t
= t6 -
the better of the
two values:
± 10 % or ± 40
ms (for a time set
< 5 s) / ± 100 ms
(for a time set
5 s)
Iinst - Defined by ABB - Instantaneous - - -
Current
thresholds
(1 and 2)
-
50…100 % I1
step = 1 %
- - - - -
Current
thresholds
(Iw1 and Iw2)
-
0.1…10 In
step = 0.01 In
- - - - -
Continued on the next page

Table of Contents

Other manuals for ABB SACE Emax E2.2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB SACE Emax E2.2 and is the answer not in the manual?

ABB SACE Emax E2.2 Specifications

General IconGeneral
BrandABB
ModelSACE Emax E2.2
CategoryCircuit breakers
LanguageEnglish

Related product manuals