5.2 Faults without indication
Table 11
Error Possible Cause Remedy
The output of the indoor unit is too low. Heat exchanger of outdoor or indoor unit soiled. Clean heat exchanger of outdoor or indoor
unit.
Lack of refrigerant Check tightness of pipes, reseal if required.
Refill refrigerant.
Outdoor unit or indoor unit is not working. No power Check power connection.
Power on the indoor unit.
RCD or fuse Fuse has tripped. Check power connection.
Check RCD or fuse.
Outdoor unit or indoor unit starts and stops
continuously.
Insufficient refrigerant in the system. Check tightness of pipes, reseal if required.
Refill refrigerant.
Too much refrigerant in the system. Remove refrigerant with refrigerant recovery
unit.
Moisture or impurities in the refrigerant circuit. Evacuate refrigerant circuit.
Fill with new refrigerant.
Voltage fluctuations too high. Install voltage regulator.
Defective compressor. Replace compressor.