EasyManuals Logo
Home>ComAp>Controller>InteliCompact NT

ComAp InteliCompact NT Reference Guide

ComAp InteliCompact NT
291 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #160 background imageLoading...
Page #160 background image
InteliCompact
NT
, SW version 2.1
InteliCompact-NT-2.1-Reference Guide.pdf, ©ComAp – May 2015
160
16 Appendix
16.1 Table of setpoints
16.1.1 Group: Process Control
Setpoint: Baseload
Group
Process Control
Range [units]
0 … Nominal power [kW]
Related
applications
SPtM
Description
Required gen-set load in parallel to mains operation.
Setpoint: Base PF
Group
Process Control
Range [units]
0.7 ... 1.0 [-]
Related
applications
SPtM
Description
Required gen-set power factor when the gen-set is running parallel to the
mains.
Setpoint: AMFStartEnable
Group
Process Control
Range [units]
NO, YES [-]
Related
applications
SPtM
Description
Use this setpoint to enable or disable the AMF operation.
Setpoint: Export Limit
Group
ProcessControl
Range [units]
DISABLED, ENABLED [-]
Related
applications
SPtM
Description
Tells controller to activate protection against power export to the Mains. The
function limits gen-set requested power to hold export power lower or equal
to the setpoint Export kW.

Table of Contents

Other manuals for ComAp InteliCompact NT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliCompact NT and is the answer not in the manual?

ComAp InteliCompact NT Specifications

General IconGeneral
BrandComAp
ModelInteliCompact NT
CategoryController
LanguageEnglish

Related product manuals