8 Values
Values (or quantities) are analog or binary data objects, measured or computed by the controller, that
are intended for reading from the controller screen, PC, MODBUS, etc. Values are organized into
groups according to their meaning.
NOTE:
A complete overview of all data objects available in the controller can be exported by LiteEdit into a
text file. Open any connection (also offline with a previously saved archive) and go to the menu
Controller -> Generate CFG image.
8.1 Invalid flag
If valid data is available for a particular value, the invalid flag is set to it. This situation may be due to
the following:
The value is not being evaluated in the scope of the current application and configuration.
Sensor fail has been detected on an analog input.
The configured ECU or extension module does not provide the particular value.
The communication with the ECU or extension module is interrupted.
A value containing the invalid flag is displayed as “####” in LiteEdit and on the controller screen. If
such a value is read out via Modbus, it will contain the data 32768 in the case of signed values and
65535 in the case of unsigned values.
8.2 Value groups
1. Engine
2. Generator
3. Mains
4. Bus
5. Pwr Management
6. Controller I/O
7. Extension I/O
8. Statistics
9. Date/Time
10. Info
8.2.1 Values – Engine
1. RPM
2. W-TerminalFreq
3. ECU State
4. Fuel Rate ECU
5. Cool Temp ECU
6. IntakeTemp ECU
7. Oil Press ECU
8. Oil Temp ECU
9. BoostPress ECU
10. Perc Load ECU
11. FuelLevel ECU