220
Value: Perc Load ECU
Group
Engine
Units
%
Related
applications
All
Description
Percent load at current speedvalue obtained from the ECU. Contains
invalid flag if ECU is not configured or if the particular ECU does not provide
this value.
Value: FuelLevel ECU
Group
Engine
Units
%
Related
applications
All
Description
Fuel level obtained from the J1939 bus. Contains invalid flag if ECU is not
configured or if the particular ECU does not provide this value.
Value: ECU FreqSelect
Group
Engine
Units
-
Related
applications
All
Description
Shows selected frequency of ECU. 0” means PRIMARY, “1” is
SECONDARY and “##### is DEFAULT.
Value: Speed Request
Group
Engine
Units
%
Related
applications
All
Description
Engine speed control via CAN bus.
Speed request
Requested speed
Accelerator pedal position
0%
1350 RPM
0%
50%
1500 RPM
50%
100%
1650 RPM
100%
NOTE:
This function (speed adjust via CAN bus) has to be supported by the engine
ECU. Without the support, ComAp controllers can not adjust the engine
speed.

Table of Contents

Other manuals for ComAp InteliCompact NT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliCompact NT and is the answer not in the manual?

ComAp InteliCompact NT Specifications

General IconGeneral
BrandComAp
ModelInteliCompact NT
CategoryController
LanguageEnglish

Related product manuals