Binary output: MCB UV Coil
This output is to be used for control of the undervoltage coil of the mains
circuit breaker. See the chapter Circuit breakers for details about all outputs
available for generator/mains power switches.
Binary output: Ready To AMF
The output is closed if the gen-set is ready to start automatically and take
the load if the mains fails, i.e.:
ï‚· the gen-set is not running and
ï‚· the controller is in AUT mode and
ï‚· no red alarm is present in the alarmlist
Binary output: Mains Healthy
This output is active while mains failure is not detected, i.e. the mains are
healthy.
Binary output: Mains Fail
This output is active while mains failure is detected.
This output is active whenever the controller is in TEST mode.
16.5 Table of internal alarms
Alarm: Emergency Stop