InteliCompact
NT
, SW version 2.1
InteliCompact-NT-2.1-Reference Guide.pdf, ©ComAp – May 2015
274
Binary output: MCB UV Coil
Related
applications
SPtM
Description
This output is to be used for control of the undervoltage coil of the mains
circuit breaker. See the chapter Circuit breakers for details about all outputs
available for generator/mains power switches.
Binary output: Ready To AMF
Related
applications
SPtM
Description
The output is closed if the gen-set is ready to start automatically and take
the load if the mains fails, i.e.:
ï‚· the gen-set is not running and
ï‚· the controller is in AUT mode and
ï‚· no red alarm is present in the alarmlist
Binary output: Mains Healthy
Related
applications
SPtM
Description
This output is active while mains failure is not detected, i.e. the mains are
healthy.
Binary output: Mains Fail
Related
applications
SPtM
Description
This output is active while mains failure is detected.
Binary output: Mode TEST
Related
applications
All
Description
This output is active whenever the controller is in TEST mode.
16.5 Table of internal alarms
Alarm: Emergency Stop
Alarm type
Shutdown
Alarmlist
message
Emergency Stop
Alarm evaluated
All the time
Related
applications
All

Table of Contents

Other manuals for ComAp InteliCompact NT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliCompact NT and is the answer not in the manual?

ComAp InteliCompact NT Specifications

General IconGeneral
BrandComAp
ModelInteliCompact NT
CategoryController
LanguageEnglish

Related product manuals