current power band. Setpoint is taken into account only if #PriorAutoSwap =
EFFICENT.
16.1.8 Group: AMF Settings
Setpoint: EmergStart Del
Delay between the mains failure and the automatic start of the gen-set to an
AMF operation. See more in the AMF operation chapter.
This is a “mains stabilization” time. If the mains are continuously healthy for
this period after they have returned, the controller will finish the AMF
operation (e.g. by reverse synchronization or a switchover). See more in the
AMF operation chapter.
Threshold for detection of mains failure due to overvoltage. The setpoint is
adjusted relative to the generator nominal voltage (setpoint Nominal Volts).
Threshold for detection of mains failure due to undervoltage. The setpoint is
adjusted relative to the generator nominal voltage (setpoint Nominal Volts).