InteliCompact
NT
, SW version 2.1
InteliCompact-NT-2.1-Reference Guide.pdf, ©ComAp – May 2015
166
Setpoint: Im/EF input
Group
Basic Settings
Range [units]
Mains, EarthFltC [-]
Related
applications
SPtM
Description
This setpoint is relevant only in case IC-NT CT-BIO7 module is used. It is
then used for switching between Mains current measurement and Earth
Fault Current protection depending on the purpose of IC-NT CT-BIO7
usage.
Setpoint: Nominal Volts
Group
Basic Settings
Range [units]
80 ... 20000 [V]
Related
applications
All
Description
Nominal system voltage (phase to neutral)
Setpoint: PT Ratio
Group
Basic Settings
Range [units]
0.1 ... 500 [V/V]
Related
applications
All
Description
Generator voltage potential transformers ratio. If no PTs are used, adjust the
setpoint to 1.
Setpoint: Vm PT Ratio
Group
Basic Settings
Range [units]
0.1 ... 500 [V/V]
Related
applications
SPtM
Description
Mains voltage potential transformers ratio. If no PTs are used, adjust the
setpoint to 1.
Setpoint: Vb PT Ratio
Group
Basic Settings
Range [units]
0.1 ... 500 [V/V]
Related
applications
MINT
Description
Bus voltage potential transformers ratio. If no PTs are used, adjust the
setpoint to 1.

Table of Contents

Other manuals for ComAp InteliCompact NT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliCompact NT and is the answer not in the manual?

ComAp InteliCompact NT Specifications

General IconGeneral
BrandComAp
ModelInteliCompact NT
CategoryController
LanguageEnglish

Related product manuals