NOTE:
This output does not provide information that the reserve is already reached.
It only gives information that there is enough capacity within the gen-set
group to reach the reserve.
Binary output: SystReserve OK
The output is closed while the Actual Reserve is greater than the currently
selected reserve for start.
Binary output: EnginesSwapped
The output is activated by the master controller for 100 ms pulse when the
priority of two gen-sets was swapped by the Running Hours Equalization
function (setpoint #RunHrsMaxDiff).
16.4.5 SPtM specific
Binary output: MCB Close/Open
This output is to be used for a contactor control in case a contactor is used
in the MCB position. See the chapter Circuit breakers for details about all
outputs available for generator/mains power switches.
Binary output: MCB ON Coil
This output is to be used for control of the ON coil of the mains circuit
breaker. See the chapter Circuit breakers for details about all outputs
available for generator/mains power switches.
Binary output: MCB OFF Coil
This output is to be used for control of the OFF coil of the mains circuit
breaker. See the chapter Circuit breakers for details about all outputs
available for generator/mains power switches.