, SW version 2.1
InteliCompact-NT-2.1-Reference Guide.pdf, ©ComAp – May 2015
246
Value: CAN32
Group
Info
Units
-
Related
applications
MINT
Description
Each bit of this value shows if a controller with the corresponding address is
found on the bus. Bit 0 represents address 16 etc.
Value: GensLoaded16
Group
Info
Units
-
Related
applications
MINT
Description
Each bit if set represents gen-set with its GCB closed.
Value: GensLoaded32
Group
Info
Units
-
Related
applications
MINT
Description
Each bit if set represents gen-set with its GCB closed.
16.3 Table of binary input functions
16.3.1 Common functions
Binary input: GCB Feedback
Related
applications
All
Description
This is an input from the generator circuit breaker or contactor auxiliary
contact. If the input is active, the controller will consider the GCB as closed
and vice versa. If the GCB is not in the expected position, the alarm GCB
Fail will occur.

Table of Contents

Other manuals for ComAp InteliCompact NT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliCompact NT and is the answer not in the manual?

ComAp InteliCompact NT Specifications

General IconGeneral
BrandComAp
ModelInteliCompact NT
CategoryController
LanguageEnglish

Related product manuals