InteliCompact
NT
, SW version 2.1
InteliCompact-NT-2.1-Reference Guide.pdf, ©ComAp – May 2015
Each bit of this value shows if a controller with the corresponding address is
found on the bus. Bit 0 represents address 16 etc.
Each bit if set represents gen-set with its GCB closed.
Each bit if set represents gen-set with its GCB closed.
16.3 Table of binary input functions
16.3.1 Common functions
Binary input: GCB Feedback
This is an input from the generator circuit breaker or contactor auxiliary
contact. If the input is active, the controller will consider the GCB as closed
and vice versa. If the GCB is not in the expected position, the alarm GCB
Fail will occur.