InteliCompact
NT
, SW version 2.1
InteliCompact-NT-2.1-Reference Guide.pdf, ©ComAp – May 2015
Setpoint indicates the maximum allowable drop of fuel in fuel tank per
running hour. When the engine is not running, the maximum allowed fuel
drop-off is preset to 5% of the total tank volume per hour.
In case of detection of theft or leak, the alarm Wrn FuelTheft is raised and
the same alarm is sent via SMS and displayed by WebSupervisor (if used).
NOTE:
Set 0 to disable Fuel Theft Protection function.
Define a capacity of gen-set fuel tank.
16.1.5 Group: Engine Protect
Setpoint: Horn Timeout
Maximum time the Horn output is active. The horn always activates
whenever a new alarm occurs and can be silenced earlier by pressing the
HORN RESET button. Acknowledging alarms by pressing FAULT RESET
will silence the horn as well.
If a new alarm appears, the timeout starts to count down again from the
beginning even if the previous countdown has still not elapsed. Adjust this
setpoint to zero if you want to disable the horn completely.
Use this setpoint to adjust the delay starting evaluation of engine running
only alarms. The delay starts to count down in the moment of transition from
starting phase to the idle phase.