Nominal system frequency (usually 50 or 60Hz).
Number of teeth on the engine flywheel where the pick-up is installed. Set to
zero if no pick-up is used and the Engine speed will be counted from the
generator frequency.
NOTE:
If no pickup is used, the D+ or W terminal should be used to prevent
possible overcranking, which can occur if at least 25% of nominal generator
voltage is not present immediately after exceeding firing speed.
OFF, MAN, AUT, (TEST) [-]
This setpoint can be used for changing the operating mode remotely, e.g.
via Modbus. Use the mode selector on the main screen for changing the
mode from the front panel. Use mode selector in the control window for
changing the mode from LiteEdit.