InteliCompact
NT
, SW version 2.1
InteliCompact-NT-2.1-Reference Guide.pdf, ©ComAp – May 2015
167
Setpoint: Nominal Freq
Group
Basic Settings
Range [units]
45 ... 65 [Hz]
Related
applications
All
Description
Nominal system frequency (usually 50 or 60Hz).
Setpoint: Nominal RPM
Group
Basic Settings
Range [units]
100 ... 4000 [RPM]
Related
applications
All
Description
Nominal engine speed.
Setpoint: Gear Teeth
Group
Basic Settings
Range [units]
0 (OFF) ... 500 [-]
Related
applications
All
Description
Number of teeth on the engine flywheel where the pick-up is installed. Set to
zero if no pick-up is used and the Engine speed will be counted from the
generator frequency.
NOTE:
If no pickup is used, the D+ or W terminal should be used to prevent
possible overcranking, which can occur if at least 25% of nominal generator
voltage is not present immediately after exceeding firing speed.
Setpoint: ControllerMode
Group
Basic Settings
Range [units]
OFF, MAN, AUT, (TEST) [-]
Related
applications
All
Description
This setpoint can be used for changing the operating mode remotely, e.g.
via Modbus. Use the mode selector on the main screen for changing the
mode from the front panel. Use mode selector in the control window for
changing the mode from LiteEdit.

Table of Contents

Other manuals for ComAp InteliCompact NT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliCompact NT and is the answer not in the manual?

ComAp InteliCompact NT Specifications

General IconGeneral
BrandComAp
ModelInteliCompact NT
CategoryController
LanguageEnglish

Related product manuals