196
Range [units]
0 ... 600.0 [s]
Related
applications
SPtM
Description
Delay for detection of mains failure due to over/undervoltage.
Setpoint: Mains >Freq
Group
AMF Settings
Range [units]
Mains <Freq ... 150 [%]
Related
applications
SPtM
Description
Threshold for detection of mains failure due to overfrequency. The setpoint
is adjusted relative to the generator nominal frequency (setpoint Nominal
Freq).
Setpoint: Mains <Freq
Group
AMF Settings
Range [units]
50 ... Mains >Freq [%]
Related
applications
SPtM
Description
Threshold for detection of mains failure due to underfrequency. The setpoint
is adjusted relative to the generator nominal frequency (setpoint Nominal
Freq).
Setpoint: Mains Freq Del
Group
AMF Settings
Range [units]
0 ... 600.0 [s]
Related
applications
SPtM
Description
Delay for detection of mains failure due to over/underfrequency.
Setpoint: VectorShiftLim
Group
AMF Settings
Range [units]
1 ... 45 [°]
Related
applications
SPtM
Description
Threshold for detection of mains failure due to Vector shift. A mains failure is
detected immediately when the vector surge has occurred without any delay.
Setpoint: Transfer Del
Group
AMF Settings
Range [units]
0 ... 600 [s]

Table of Contents

Other manuals for ComAp InteliCompact NT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliCompact NT and is the answer not in the manual?

ComAp InteliCompact NT Specifications

General IconGeneral
BrandComAp
ModelInteliCompact NT
CategoryController
LanguageEnglish

Related product manuals