InteliCompact
NT
, SW version 2.1
InteliCompact-NT-2.1-Reference Guide.pdf, ©ComAp – May 2015
Limits and units depend on analog input configuration
This setpoint can be used to “calibrate” the controller analog input 2, i.e. shift
the measured value on the analog input with a constant. The setpoint
(constant) is always added to the measured analog value.
NOTE:
It is recommended to perform the calibration under operating conditions, i.e.
perform a coolant temperature sensor calibration when the engine is warm,
not cold.
Limits and units depend on analog input configuration
This setpoint can be used to “calibrate” the controller analog input 3, i.e. shift
the measured value on the analog input with a constant. The setpoint
(constant) is always added to the measured analog value.
NOTE:
It is recommended to perform the calibration under operating conditions, i.e.
perform a coolant temperature sensor calibration when the engine is warm,
not cold.
Limits and units depend on analog input configuration
This setpoint can be used to “calibrate” the analog input 1 of the extension
module IG-IOM or IGS-PTM, i.e. shift the measured value on the analog
input with a constant. The setpoint (constant) is always added to the
measured analog value.
NOTE:
It is recommended to perform the calibration under operating conditions, i.e.
perform a coolant temperature sensor calibration when the engine is warm,
not cold.