234
Value: Running Q-Pwr
Value: Running NomPwr
Group
Power management
Units
kW
Related
applications
MINT
Description
Sum of nominal power of all gen-sets within the group that are connected to
the bus and are performing the power management, i.e. that are in AUT
mode and have power management enabled.
Value: Avail Nom Pwr
Group
Power management
Units
kW
Related
applications
MINT
Description
Sum of nominal load of all active gen-sets within the group.
Value: Priority
Group
Power management
Units
-
Related
applications
MINT
Description
This value shows the current priority number. If the binary input Top Priority
is active, the priority number will be 0, otherwise the value will correspond to
the setpoint Priority. See the chapter Power management for details.
Value: Act Pwr Band
Group
Power management
Range [units]
-
Related
applications
MINT
Description
The values show which gen-sets (controller CAN addresses) are running in
current active power band.
Group
Power management
Units
kVAr
Related
applications
MINT
Description
Sum of reactive power of all gen-sets within the group that are connected to
the bus and are performing the power management, i.e. that are in AUT
mode and have power management enabled.

Table of Contents

Other manuals for ComAp InteliCompact NT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliCompact NT and is the answer not in the manual?

ComAp InteliCompact NT Specifications

General IconGeneral
BrandComAp
ModelInteliCompact NT
CategoryController
LanguageEnglish

Related product manuals