This alarm informs the operator that the controller supply voltage is too low
or too high. The following setpoints are related to it:
ï‚· Batt Undervolt adjusts the low voltage limit.
ï‚· Batt Overvolt adjusts the high voltage limit.
ï‚· Batt Volt Del adjusts the alarm delay.
Alarm: Governor output at limit
This alarm will be issued if the governor output has 0V or 10V for more than
2. This situation can occur, for example, if the Speed Gov Char setpoint is in
the wrong position or if the connection of the governor output to the governor
is not correct.
Alarm: AVR output at limit
This alarm will be issued if the governor output has 0% or 100% for more
than 2 . This situation can occur, for example, if the connection of the AVRi
output to the AVR is not correct.