EasyManuals Logo
Home>GE>Relays>469

GE 469 User Manual

GE 469
336 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #52 background imageLoading...
Page #52 background image
2–6 469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 2: INTRODUCTION
2.2 Specifications
Specifications are subject to change without notice.
2.2.1 Inputs
ANALOG CURRENT INPUTS
Inputs:..................................................................0 to 1 mA, 0 to 20mA, or 4 to 20 mA (settings)
Input impedance: ..........................................226 Ω ±10%
Conversion range: .........................................0 to 21 mA
Accuracy:............................................................±1% of full scale
Type: .....................................................................passive
Analog in supply: ...........................................+24 V DC at 100 mA max.
Response time: .....................................≤100 ms
DIFFERENTIAL CURRENT INPUTS
CT primary:........................................................1 to 5000A
CT secondary: .................................................1 A or 5 A (settings)
Burden:................................................................<0.2 VA at rated load
Conversion range: .........................................0.02 to 1 × CT primary
Nominal frequency: ......................................20 to 70 Hz
Frequency range: ..........................................20 to 120 Hz
Accuracy:............................................................±0.5% of 1 × CT for 5 A
±0.5% of 5 × CT for 1 A
CT withstand: ..................................................1 second at 80 × rated current,
2 seconds at 40 × rated current, continuous at 3 × rated
current
DIGITAL INPUTS
Inputs:..................................................................9 opto-isolated inputs
External switch: ..............................................dry contact < 400 Ω, or open collector NPN transistor
from sensor; 6 mA sinking from internal 4 KΩ pull-up at
24VDC with Vce<4VDC
See Digital Inputs on page 2–10 for additional specifications.
GROUND CURRENT INPUTS
CT primary:........................................................1 to 5000 A
CT secondary: .................................................1 A or 5 A (settings)
Burden:................................................................<0.2 VA at rated load for 1 A or 5 A; <0.25 VA for 50:0.025
CTs
at 25 A
Conversion range: .........................................0.02 to 1 × CT primary
Nominal frequency: ......................................20 to 70 Hz
Frequency range: ..........................................20 to 120 Hz
Accuracy:............................................................±0.5% of 1 × CT for 5 A CTs
±0.5% of 5 × CT for 1 A CTs
±0.125 A for 50:0.025 CTs
CT (1 A/5 A) withstand:.................................1 second at 80 × rated current,
2 seconds at 40 × rated current, continuous at 3 × rated
current
CT (50:0.025) withstand: ..............................continuous at 150 mA
PHASE CURRENT INPUTS
CT primary:........................................................1 to 5000 A

Table of Contents

Other manuals for GE 469

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE 469 and is the answer not in the manual?

GE 469 Specifications

General IconGeneral
BrandGE
Model469
CategoryRelays
LanguageEnglish

Related product manuals