IDS X-Series Training v2.7 | Advanced Miscellaneous Settings
Advanced Miscellaneous Settings
Location 32: Auto Test Interval
Location Type: Standard
The time between test signals that are sent back to the monitoring company. Every time an auto test is
done the event is automatically and sequentially numbered, the counter starts at 0 and increments to 255.
Location 33: Auto Test Time
Location Type: Standard
This is the time of day that the test signal, set in location 32, must be transmitted.
Data Format: HHmm
Valid Range: 0000 - 2359
Default: 0010
Location 34: Download Code Default Disable
Location Type: Standard
The download code is a security code to stop any illegal connection and changing of data via external
connections, using IDSwift software. If this option is enabled then defaulting the system will have no effect
on the download code.
Valid Range: 0 or 10
Location 35: Hardware Default Switch Disable
Location Type: Standard
Every system has a hardware default switch which is activated by removing power from the system and
powering up while holding the switch down until the status LED flashes. If this option is enabled then the
only way to default is via the installer code and location 0.
Enable defaulting of the default button
Disable the defaulting of the default button
Enable Download code defaulting
Disable Download code defaulting