Goodrive35 Series Closed-loop Vector Control VFD Communication protocol
231
After receiving the command, the VFD converts 50 into 5.0 based on the fieldbus scale, and then sets
"Wake-up-from-sleep delay" to 5.0s.
For another example, after the upper computer transmits the "Wake-up-from-sleep delay" parameter
read command, the master receives the following response from the VFD:
VFD
address
Read
command
Parameter
data
CRC check
2-byte
data
01 03 02 00 32 39 91
The parameter data is 0032H, that is, 50, so 5.0 is obtained based on the fieldbus scale (50/10=5.0).
In this case, the master identifies that the "Wake-up-from-sleep delay" is 5.0s.
10.4.7 Fault message response
Operation errors may occur in communication-based control. For example, some parameters can
only be read, but a write command is transmitted. In this case, the VFD returns an error message
response.
Error message responses are transmitted by the VFD to the master. The following table describes the
codes and definitions of the error message responses.
The command code received by the upper computer is not allowed
to be executed. The possible causes are as follows:
• The function code is applicable only on new devices and is not
implemented on this device.
• The slave is in the faulty state when processing this request.
For the VFD, the data address in the request of the upper computer
is not allowed. In particular, the combination of the register address
and the number of the to-be-transmitted bytes is invalid.
The received data domain contains a value that is not allowed. The
value indicates the error of the remaining structure in the combined
request.
Note: It does not mean that the data item submitted for storage in
the register includes a value unexpected by the program.
The parameter is set to an invalid value in the write operation. For
example, a function input terminal cannot be set repeatedly.
The password entered in the password verification address is
different from that set in P07.00.
The length of the data frame transmitted by the upper computer is
incorrect, or in the RTU format, the value of the CRC check bit is
inconsistent with the CRC value calculated by the lower computer