Goodrive35 Series Closed-loop Vector Control VFD Optional peripheral accessories
276
Recommended
cable size (mm
2
)
Connecting cable size (mm
2
)
Note:
1. Cables of the sizes recommended for the main circuit can be used in scenarios where the ambient
temperature is lower than 40°C, the wiring distance is shorter than 100 m, and the current is the rated
current.
2. The terminals P1, (+), and (-) are used to connect to DC reactors and brake accessories.
D.4.3 Routing the cables
Motor cables must be arranged away from other cables. The motor cables of several VFDs can be
arranged in parallel. It is recommended that you arrange the motor cables, input power cables, and
control cables separately in different trays. The output dU/dt of the VFDs may increase
electromagnetic interference on other cables. Do not arrange other cables and the motor cables in
parallel.
If a control cable and power cable must cross each other, ensure that the angle between them is 90
degrees.
The cable trays must be connected properly and well grounded. Aluminum trays can implement local
equipotential.
The following figure shows the cable arrangement distance requirements.