IPE300 series engineering VFD Function parameter list
-111-
parameters. Incorrect parameter setting may cause operation exceptions or even damage to the
VFD.) If password protection is not in locked state, you can change the password any time. You
can set P07.00 to 0 to cancel the user password. When P07.00 is set to a non-zero value during
power-on, parameters are prevented from being modified by using the user password function.
When you modify function parameters through serial communication, the user password
protection function is also applicable and compliant with the same rule.
P00 group––Basic functions
Function
code
Name
Description
Default
Modify
P00.00
Speed control
mode
0: Sensorless vector control (SVC) mode 0
1: Sensorless vector control (SVC) mode 1
2: Space voltage vector control mode
3: Closed-loop vector control mode
Note: If 0, 1 or 3 is selected, it is required to
carry out motor parameter autotuning first.
2
â—Ž
P00.01
Channel of running
commands
0: Keypad
1: Terminal
2: Communication
0
â—‹
P00.02
Communication
mode of running
commands
0: Modbus
1: PROFIBUS/CANopen/DeviceNet
2: Ethernet
3: EtherCAT/Profinet
4: Programmable extension card
5: Wireless communication card
Note: The options 1, 2, 3, 4, and 5 are add-on
functions and are available only when
corresponding extension cards are configured.
0
â—‹
P00.03
Max. output
frequency
Used to set the max. output frequency of the
VFD. Pay attention to the function code
because it is the foundation of the frequency
setting and the speed of acceleration (ACC)
and deceleration (DEC).
Setting range: Max(P00.04, 10.00)–630.00Hz
50.00Hz
â—Ž
P00.04
Upper limit of
running frequency
The upper limit of the running frequency is the
upper limit of the output frequency of the VFD,
which is lower than or equal to the max. output
frequency.
When the set frequency is higher than the
upper limit of the running frequency, the upper
50.00Hz
â—Ž