IPE300 series engineering VFD Function parameter list
-226-
AO2 output
corresponding to
lower limit
value exceeds the allowed range, the output uses
the lower limit or upper limit.
When the analog output is current output, 1mA
equals 0.5V.
In different cases, the corresponding analog
output of 100% of the output value is different.
Setting range of P26.38: -100.0%–P26.40
Setting range of P26.39: 0.00V–10.00V
P26.40 setting range: P26.38–100.0%
P26.41 setting range: 0.00V–10.00V
P26.42 setting range: 0.000s–10.000s
P26.43 setting range: -100.0%–P26.45
P26.44 setting range: 0.00V–10.00V
P26.45 setting range: P26.43–100.0%
P26.46 setting range: 0.00V–10.00V
P26.47 setting range: 0.000s–10.000s
AO2 output
corresponding to
upper limit
AO3 output
corresponding to
lower limit
AO3 output
corresponding to
upper limit
P28 group––Master/slave control
0: Master/slave control is invalid.
1: The local device is the master.
2: The local device is the slave.
Master/slave
communication
data selection
0: CAN
1: RS485 (Reserved)
Master/slave
control
multifunction
mode
Ones place: Master/slave running mode
0: Master/slave mode 0
(Both the master and slave use speed control,
and power balancing is performed by droop