IPE300 series engineering VFD Quick startup
-7-
2.6 Basic commissioning
Complete the basic commissioning as follows before the actual use of the VFD:
1. According to the actual motor parameters, select the motor type, set motor parameters, and
select the VFD control mode.
2. Check whether autotuning is required. If possible, de-couple the VFD from the motor load to
start dynamic parameter autotuning. If the VFD cannot be de-coupled from the load, perform
static autotuning.
3. Adjust the ACC/DEC time according to the actual work condition of the load.
4. Perform device commissioning by means of jogging and check whether the motor rotational
direction is correct. If not, change the rotation direction by swapping any two phase wires of
the motor.
5. Set all control parameters and then perform actual run.
2.7 Safety standard related data
IEC/EN 61508 (Class A system)
ISO 13849**
SIL
PFH
HFT
SFF
λdu
λdd
PTI*
PL
CCF
MTTFd
DC
Category
2
8.73x10
-10
1
71.23%
1.79x10
-9
0
1 year
d
57
343.76
years
60%
3
* PTI: Proof test interval
** Depends on the the classification defined on the EN ISO 13849-1.