IPE300 series engineering VFD Function parameter list
-244-
1: VFD stops when: the detected temperature
exceeds the overtemp threshold; the detected
resistance exceeds the overtemp protection
resistance; PTC selected by terminal function
is enabled; or the overtemp fault E-OHt is
reported.
AIAO
disconnection
detection
0: Disable
1: Enable. When the disconnection is detected,
the fault A-OPn is reported and the action in
P93.29 is conducted.
0: Normal running
1: Decelerate to stop
AIAO detected
temperature
compensation
value
P94 group––Braking control functions
0: With feedback signal
1: Without feedback signal
Execute the release operation after the VFD
output frequency rises to the release frequency.
Range: 0.20–20.00Hz
Execute the release operation after the VFD
output current rises to the release current.
Range: 0.0–P94.10
Delay time
before brake
release
Hold time before executing release operation.
Range: 0.000–5.000s
Delay time after
brake release
Hold time after executing release operation.
Range: 0.000–5.000s
Execute the brake switch-on operation after the
VFD output frequency drops to the braking
frequency.
Range: 0.20–20.00Hz