IPE300 series engineering VFD Function parameter list
-245-
Delay time
before brake
switch-on
Hold time before executing brake switch-on
operation.
Range: 0.000–5.000s
Delay time after
brake switch-on
Hold time after executing brake switch-on
operation.
Range: 0.000–5.000s
Brake feedback
exception
detection time
When the brake command and the brake
feedback signal are not consistent, the fault will
be reported after the delay of P94.09.
Range: 0.000–20.000
Electromotive
torque upper limit
at brake
switch-on
Indicates the electromotive torque upper limit at
brake switch-on.
Range: 0.0– 200.0% of the motor rated current
Braking torque
upper limit at
brake switch-on
Indicates the braking torque upper limit at brake
switch-on.
Range: 0.0– 200.0% of the motor rated current