IPE300 series engineering VFD Function parameter list
-241-
P93 group––PT100/PT1000 temperature protection functions
Function
code
Name
Description
Default
Modify
P93.00
PT100/PT1000
temperature
detection
enabling
0x00–0x11
Ones place: PT100 temperature detection
0: Disable
1: Enable
Tens place: PT1000 temperature detection
0: Disable
1: Enable
0x00
â—Ž
P93.01
PT100
overtemperature
protection point
0.0–150.0°C
100.0°C
â—‹
P93.02
PT100
overtemperature
pre-alarm point
0.0–150.0°C
85.0°C
â—‹
P93.03
Upper limit of
PT100
calibration
temperature
50.0–150.0°C
150.0°C
â—‹
P93.04
Lower limit of
PT100
calibration
temperature
-20.0–50.0°C
-20.0°C
â—‹
P93.05
Upper limit of
PT100
calibration digital
quantity
0–4096
3800
â—‹
P93.06
Lower limit of
PT100
calibration digital
quantity
0–4096
0
â—‹
P93.07
PT1000
overtemperature
protection point
0.0–150.0°C
100.0°C
â—‹
P93.08
PT1000
overtemperature
pre-alarm point
0.0–150.0°C
85.0°C
â—‹
P93.09
Upper limit of
PT1000
calibration
temperature
50.0–150.0°C
150.0°C
â—‹