IPE300 series engineering VFD Function parameter list
-174-
Function
code
Name
Description
Default
Modify
or fault), it will record the running time of current
step, and enters this step automatically after
restart, then continue running at the frequency
defined by this step in the remaining time.
P10.37
Multi-step
time unit
0: second; the running time of each step is
counted in seconds
1: minute; the running time of each step is
counted in minutes
0
â—Ž
P11 group––Protection parameters
Function
code
Name
Description
Default
Modify
P11.00
Protection
against phase
loss
0x000–0x111
Ones place:
0: Software input phrase loss protection
disabled
1: Software input phrase loss protection
enabled
Tens place:
0: Output phrase loss protection disabled
1: Output phrase loss protection enabled
Hundreds place:
0: Hardware input phrase loss protection
disabled
1: Hardware input phrase loss protection
enabled
0x110
â—‹
P11.01
Frequency drop
at transient
power-off
0: Disable
1: Enable
0
â—‹
P11.02
Reserved
0–65535
0
â—‹
P11.03
Overvoltage
stalling
protection
0: Disable
1: Enable
Overvoltage stall
threshold
Output
frequency
Time t
Time t
DC bus voltage V
1
â—‹