IPE300 series engineering VFD Function parameter list
-174-
or fault), it will record the running time of current
step, and enters this step automatically after
restart, then continue running at the frequency
defined by this step in the remaining time.
0: second; the running time of each step is
counted in seconds
1: minute; the running time of each step is
counted in minutes
P11 group––Protection parameters
Protection
against phase
loss
0x000–0x111
Ones place:
0: Software input phrase loss protection
disabled
1: Software input phrase loss protection
enabled
Tens place:
0: Output phrase loss protection disabled
1: Output phrase loss protection enabled
Hundreds place:
0: Hardware input phrase loss protection
disabled
1: Hardware input phrase loss protection
enabled
Frequency drop
at transient
power-off
Overvoltage
stalling
protection
Overvoltage stall
threshold
Output
frequency
Time t
Time t
DC bus voltage V