533
5. PARAMETERS
5.12 (N) Operation via communication and its settings
3
4
5
5
5
6
7
8
9
10
5.12.9 Automatic connection with GOT
When the automatic connection is enabled in the GOT2000 series, the inverter can communicate with the GOT2000 series
with only setting the station number and connecting the GOT. This eliminates the need for the communication parameter
setting.
*1 When Pr.549 Protocol selection = "1" (MODBUS RTU protocol), the setting range is as shown in the parentheses.
*2 When the set value is outside of the setting range, the initial value is applied.
Automatic connection system configuration
Pr. Name Initial value Setting range Description
117
N020
PU communication station
number
0 0 to 31 Set the inverter station numbers.
The inverter station number setting is required when
multiple inverters are connected to one GOT (PU
connector communication).
331
N030
RS-485 communication
station number
0 0 to 31
(0 to 247)
*1*2
Set the inverter station numbers.
The inverter station number setting is required when
multiple inverters are connected to one GOT (RS-485
terminal communication).
GOT2000
Terminating resisto
r
Four-wire multidrop

Table of Contents

Other manuals for Mitsubishi Electric FR-F800

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Electric FR-F800 and is the answer not in the manual?

Mitsubishi Electric FR-F800 Specifications

General IconGeneral
BrandMitsubishi Electric
ModelFR-F800
CategoryInverter
LanguageEnglish

Related product manuals