Chapter 7 System Troubleshooting Gen 3 Site Controller System Manual
EAS/EAS2 Unit
7-6 68P80801E30-A 5/1/2002
EAS/EAS2 Unit
Table 7-2 EAS/EAS2 troubleshooting
Indication Possible failure Corrective action
EAS/IMU breaker on Cabinet breaker
is on, but POWER LED (green) on
EAS/EAS2 is not lit.
No power connected to EAS/
EAS2.
Check power source.
cabling Check power cabling to EAS/EAS2;
replace cable if necessary.
Wrong EAS/EAS2 response miswired modular cable Check EAS/EAS2 modular cabling.
AC fail alarm AC input, or an open or
disconnected alarm lead
Verify AC input, check for open or
disconnected alarm leads.
High temperature alarm AC input to air conditioner Verify AC input.
site air conditioner Call for service on air conditioner.
Alarm sensor improperly set
or wires shorted.
Check and adjust alarm sensor.
Alarm sensor located in a hot
spot.
Check and adjust alarm sensor.
Low temperature alarm Air conditioner does not shut
off.
Repair HVAC.
Thermostat is set too low. Set thermostat to 78˚ F.
Cold air blowing on alarm
sensor.
Shield or relocate sensor.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Motorola iDEN Site Controller and is the answer not in the manual?

Motorola iDEN Site Controller Specifications

General IconGeneral
BrandMotorola
ModeliDEN Site Controller
CategoryController
LanguageEnglish

Related product manuals