Chapter 7 System Troubleshooting Gen 3 Site Controller System Manual
EAS/EAS2 Unit
7-6 68P80801E30-A 5/1/2002
EAS/EAS2 Unit
Table 7-2 EAS/EAS2 troubleshooting
Indication Possible failure Corrective action
EAS/IMU breaker on Cabinet breaker
is on, but POWER LED (green) on
EAS/EAS2 is not lit.
No power connected to EAS/
EAS2.
• Check power source.
cabling • Check power cabling to EAS/EAS2;
replace cable if necessary.
Wrong EAS/EAS2 response miswired modular cable • Check EAS/EAS2 modular cabling.
AC fail alarm AC input, or an open or
disconnected alarm lead
• Verify AC input, check for open or
disconnected alarm leads.
High temperature alarm AC input to air conditioner • Verify AC input.
site air conditioner • Call for service on air conditioner.
Alarm sensor improperly set
or wires shorted.
• Check and adjust alarm sensor.
Alarm sensor located in a hot
spot.
• Check and adjust alarm sensor.
Low temperature alarm Air conditioner does not shut
off.
• Repair HVAC.
Thermostat is set too low. • Set thermostat to 78˚ F.
Cold air blowing on alarm
sensor.
• Shield or relocate sensor.