Chapter 10 Environmental Alarm System Gen 3 Site Controller System Manual
EAS Functional Description
10-4 68P80801E30-A 5/1/2002
The Site Controller and EAS interact in a master/slave relationship. The Site
Controller sends commands to the EAS to determine the status of alarm
inputs or set the state of control outputs. The EAS, in turn, sends alarm
status responses to the Site Controller.
The EAS continuously scans the status of the alarm inputs, ensuring that all
alarms are consistently monitored.
TO OCTAL
BUFFERS
OUTPUT
ENABLE
CONTROLLER A-
PARALLEL
CONNECTOR
TEBTS029
122396JNM
OCTAL
BUFFER
CHANGE
DETECT
LOGIC
OCTAL
LATCH
ADDRESS
DECODE
IEEE 1284
INTERFACE
IEEE 1284
INTERFACE
CONTROLLER B-
PARALLEL
CONNECTOR
48
DC-DC
CONVERTER
+5 VDC+12 VDC
-48 VDC FROM
BATTERY
CONNECTOR
OPTO-
ISOLATOR
(X48)
OCTAL
BUFFER
RELAY
(X8)
18
18
ADDRESS
DATA
7
1 2
1
8
BOARD ID RESISTORS
48
USER ALARM/CONTROL
SYSTEM ALARM/CONTROL
RFI-RF3
CONTROL
CONTROL
SYSTEM ALARM/CONTROL
USER ALARM/CONTROL
3
2
3
ADDRESS
LATCH
Figure 10-2 EAS Block Diagram

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Motorola iDEN Site Controller and is the answer not in the manual?

Motorola iDEN Site Controller Specifications

General IconGeneral
BrandMotorola
ModeliDEN Site Controller
CategoryController
LanguageEnglish

Related product manuals