AFP-3030 Programming Manual — P/N DOC-01-032:A 26/06/2015 101
Mass Notification Special Zone Outputs
B.2 Mass Notification
When used for mass notification, special zones ZF20, ZF21, and ZF22 can be used to signal the
MN events.
ZF20 - MN Alarm
When an MN Alarm condition exists on the fire panel:
• ZF20 will activate and any CBE activations will be initiated.
• ZF20 activation is sent over the network.
• The OTHER LED will flash. (on steady after Acknowledged)
• The piezo will sound a steady audible tone. (silent after Acknowledged)
• Any devices programmed as General Pending will activate.
• Any alarm relays or devices programmed as General Alarm or Alarm Pending type codes do
not activate.
• Any devices programmed as “Resound by Fire” will not activate.
• If the fire panel is programmed so that MN events have priority over fire events, and a fire
condition exists on the fire panel, any fire activation(s) will be suppressed locally as well as
for any network nodes that MN mapped to the panel via VeriFire Tools.
• The MN Alarm message will not be sent to the proprietary receiver via the network.
• If the ZF20 activation is received from the network and the fire panel is All Systems
Normal, “NETWORK MN ACTIVE” is displayed on the status bar of the fire panel.
ZF21 - MN Supervisory
When an MN Supervisory condition exists on the fire panel:
• ZF21 will activate and any CBE activations will be initiated.
• ZF21 activation is sent over the network.
• The SUPERVISORY LED will flash. (on steady after Acknowledged)
• The piezo will sound a warbling audible tone. (silent after Acknowledged)
• Any devices programmed as General Pending will activate.
• Any devices programmed as General Supervisory will not activate.
• Any devices programmed as “Resound by Supervisory” will not activate.
• The fire panel’s Supervisory relay will not activate.
• The MN Supervisory message is sent to the proprietary receiver via the network.
• If the fire panel is programmed so that MN events have priority over fire events, and a fire
condition exists on the fire panel, an MN Supervisory will not suppress any fire alarms
locally or for any network nodes that MN mapped to the panel via VeriFire Tools.
ZF22 - MN Fault
When an MN fault condition exists on the fire panel:
• ZF22 will activate and any CBE activations will be initiated.
• ZF22 activation is sent over the network.
• The FAULT LED will flash. (on steady after Acknowledged)
• The piezo will sound a pulsed audible tone. (silent after Acknowledged)
• Any devices programmed as General Pending, Fault Pending and General Fault will
activate.
• Any devices programmed as “Resound by Fault” will not resound.
• The fire panel’s Fault relay will activate.
• The MN Fault message is sent to the proprietary receiver via the network.