AFP-3030 Programming Manual — P/N DOC-01-032:A 26/06/2015 79
Clear Verify Counters Alter Status
Figure 4.6 Change Alarm Sensitivity Screen
Soft Keys
OCCUPIED ALARM: The type of alarm/prealarm will display based on which soft key was
pressed in the previous screen. For example, in the screen above, OCCUPIED ALARM displays
because the OCCUPIED ALARM SENSITIVITY: soft key was pressed.
The detector sensitivity values display below the soft key. Select a value by pressing the soft key
until the desired value appears in the underlined field.
ACCEPT: Press to accept the change made on this screen, and to return to the previous screen.
4.2 Clear Verify Counters
The Clear Verify Counters screen lets you clear all counters for detectors selected for Alarm
Verification on the FACP. It displays when the “CLEAR VERIFY COUNTERS” soft key is pressed
on the Alter Status Menu screen.
Figure 4.7 Clear Verify Counters Screen
Soft Keys
CLEAR COUNTERS: Press this soft key to clear all verification counters.
LAKEVIEW GENERAL HOSPITAL
SYSTEM NORMAL
10:22:34A TUE JAN 25, 2011
ADDRESS: L03D052
AUTOMATIC INACTIVE
ELEVATOR LOBBY EAST WING
FIFTH FLOOR Z003 SMOKE(PHOTO)
OCCUPIED ALARM =6,
1= 0.50%, 6= 1.66%
2= 0.73%, 7= 1.89%
3= 0.96%, 8= 2.12% ACCEPT
4= 1.19%, 9= 2.35%
5= 1.43%,
BACK