AFP-3030 Programming Manual — P/N DOC-01-032:A 26/06/2015 135
Basic Programming: Smoke Control Modules Smoke Control Station Programming
If ACTION ON CBE is set to START, the USE SINGLE START/STOP setting is set to NO,
and a Duct Detector Zone is defined:
ZLstart = AND(Fan CBE Zone,ZLduct)
ZLstart in this scenario is used to start the fan. In this situation, it will activate when the
Fan CBE Zone (mapped to smoke detectors) activates and the duct detector is off. ZLstart
will deactivate if ZLduct activates. ZLstart will restart the fan 60 seconds after the Duct
Detector Zone deactivates if the Fan CBE Zone is still active. ZLstart should be the second
CBE zone of the duct detector and mapped to the Fan Start Point
ZLstop = NOT(ZLstart)
ZLstop in this scenario is used to stop the fan. In this situation, it will activate when
ZLstart is inactive and will deactivate when ZLstart is active. ZLstop will be the third
CBE zone of the duct detector and mapped to the Fan Stop Point.
If ACTION ON CBE is set to STOP, the USE SINGLE START/STOP setting is set to NO and
a Duct Detector Zone is defined:
ZLstart = NOT(ZLstop)
ZLstart in this scenario is used to start the fan. In this situation will activate when ZLstop
is inactive and will deactivate when ZLstop activates. ZLstart will be as the third CBE
zone of the duct detector and mapped to the Fan Start Point.
ZLstop = OR(Fan CBE Zone,NOT(ZLduct))
ZLstop in this scenario is used to stop the fan. In this situation, it will activate when either
the Fan CBE Zone is active or Duct Detector Zone is active or if the Duct Detector Zone is
off but still within the Duct Detector Delay time (defined in the ZLduct logic equation).
ZLstop will be the second CBE zone of the duct detector and mapped to the Fan Stop
Point.
If ACTION ON CBE is set to START, the USE SINGLE START/STOP is set to YES, and a
Duct Detector Zone is defined:
ZLstart in this scenario should be the second CBE zone for the duct detector and mapped
to the Fan Start Point.
If ACTION ON CBE is set to STOP, the USE SINGLE START/STOP is set to YES, and a
Duct Detector Zone is defined:
ZLstop in this scenario should be the second CBE zone for the duct detector and mapped
to the Fan Stop Point.
If ACTION ON CBE is set to START, the USE SINGLE START/STOP is set to NO, and no
Duct Detector Zone has been defined:
ZLstop = NOT(Fan CBE Zone)
ZLstop in this scenario is used to stop the fan and will activate when the Fan CBE Zone is
not active.
If ACTION ON CBE is set to START, the USE SINGLE START/STOP is set to NO, and no
Duct Detector Zone has been defined:
ZLstart = NOT(Fan CBE Zone)
ZLstart in this scenario is used to start the fan and will activate when the Fan CBE Zone is
not active.
H.5 Basic Programming: Smoke Control Modules
Fan Module
By default, the Fan Start/Stop Module SILENCEBABLE option is set to YES W/ RESOUND
FIRE.
To inhibit the Fan Start/Stop Module from being deactivated from the Silence/Resound Alarm but-
ton on the keypad, set the Fan Start/Stop Module SILENCEABLE option to NO.
When using smoke control operation, L1M159 must not be programmed or used, as this module is
reserved for programming blank switch groups on the SCS modules.

Table of Contents

Other manuals for Notifier AFP-3030

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier AFP-3030 and is the answer not in the manual?

Notifier AFP-3030 Specifications

General IconGeneral
BrandNotifier
ModelAFP-3030
CategoryControl Panel
LanguageEnglish

Related product manuals