66 AFP-3030 Programming Manual — P/N DOC-01-032:A 26/06/2015
PrealarmProgram Point Program
Add Node Offline Fault
Node offline faults can be added to fault zone programming to act as a means of affecting an output
in the event a node goes online or offline.
Adding a node offline fault to the fault zone equation is done in the same manner as described in
the
, "Logic Zone Programming" section on page 62. However, the POINT SELECT option is not
available. To add the node offline fault, place the cursor in the desired position and type in NO###,
where the ### represents the network node that is being monitored for the fault. Refer to the fol
-
lowing fault zone programming examples:
OR(NO22,NO25,NO159) - In this example, if Node 22, Node 25, or Node 159 go offline, then the
fault zone will turn ON. Once the nodes all return to their online status, the fault zone returns to
OFF. Other parameters (detectors, modules, zones, etc.) can be used in this equation as well.
OR(RANGE(NO78,NO81)) - In this example, if Nodes 78, 79, 80, and 81 go offline, the fault
zone will turn ON. Once any one of the nodes return to the online status, the fault zone returns to
OFF. Other parameters (detectors, modules, zones, etc.) can be used in this equation as well.
3.4.6 Annunciator Board Label
When ACS BOARD is selected from the Point Program Menu, the ACS Label Menu appears.
Figure 3.53 ACS Label Menu Screen (1)
Soft Keys
ACS LABEL: Type a label for the selected annunciator. The label can have up to 40 characters.
FAULT REPORTING DELAY: Smoke Control Systems only: Adjustable fault timer for FSCS.
Programmable range is 0 to 180 seconds. Default: 10
PAIRING: Smoke Control Systems only: Select group 1, 2 or 3 to pair up to eight (8) FSCS
boards so that multiple smoke control modules can act as a single unit. If enabled, each FSCS
address can only be assigned to one group and each group can be assigned up to eight (8) FSCS
addresses, Default: X
PAIRED FSCS: Smoke Control Systems only: Displays any FSCS boards that have been paired
to this annunciator.
ACCEPT: Press to insert the logic function into the equation where the cursor is blinking, and to
return to the previous screen.
Press the MORE softkey to display the second ACS label screen.