AFP-3030 Programming Manual — P/N DOC-01-032:A 26/06/2015 103
Appendix C: Intelligent Sensing Applications
C.1 Intelligent Sensing Overview
Intelligent Sensing is a set of software algorithms that provide the AFP-3030 with industry-leading
smoke detection capability. The user can program Intelligent Sensing functions on a global or on a
per-detector basis.
Intelligent Sensing topics covered in this appendix:
C.2 Intelligent Sensing Features
Intelligent Sensing features include the following:
Drift Compensation and Smoothing
Maintenance Warnings - Three Levels
Self-optimizing Pre-Alarm
Detector Sensitivity
Cooperative Multi-Detector Sensing
C.2.1 Drift Compensation and Smoothing
Drift compensation uses algorithms that identify and compensate for long-term changes in the
analog readings from each smoke detector. (Typically, dirt and dust accumulation inside the smoke
chamber causes long-term changes in detector readings.) Drift compensation does the following:
Allows a detector to retain its original ability to detect actual smoke, and resist false alarms,
even as dirt and dust accumulates.
Reduces maintenance requirements by allowing the control panel to automatically perform
periodic sensitivity measurements.
The software also provides smoothing filters to remove transient noise signals, usually caused by
electrical interference. Different smoothing algorithms are used, depending on the sensitivity
selection of each detector. Refer to
Appendix C.4, “Detector Sensitivity Settings”, on page 107 for
more information on detector sensitivity levels.
Topic Page
Intelligent Sensing features – Descriptions of Intelligent Sensing features, such as
Drift Compensation, Sensitivity Adjust, programmable on a per-detector basis.
103
Pre-Alarm – Alert and Action settings, programming (global settings). 106
Detector Sensitivity Settings – Pre-Alarm and Alarm sensitivity settings for photo, ion,
laser, and multisensor detectors programmable on a per-detector basis.
107
Detector Maintenance Features – Instructions for viewing and printing detector
maintenance information.
109

Table of Contents

Other manuals for Notifier AFP-3030

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier AFP-3030 and is the answer not in the manual?

Notifier AFP-3030 Specifications

General IconGeneral
BrandNotifier
ModelAFP-3030
CategoryControl Panel
LanguageEnglish

Related product manuals