AFP-3030 Programming Manual — P/N DOC-01-032:A 26/06/2015 23
Panel Program PrealarmProgram
3.2.4 Panel Settings
Press the Panel Settings soft key on the Panel Program Menu 1 screen to choose panel settings.
Figure 3.6 Panel Settings (1) Screen
Soft Keys
LOCAL CONTROL: Press this soft key to toggle between YES and NO. This option disables (NO) or
enables (YES) local panel control of the Signal Silence, System Reset, and Drill Fixed Function keys, as
well as SIGNAL SILENCE, SYSTEM RESET, and ACKNOWLEDGE soft keys. A setting of NO (disable)
turns the panel piezo sounder off, overriding the next field if PIEZO is set to ON. Default: YES
PIEZO: Press this soft key to toggle between OFF and ON. This option enables (ON) or disables
(OFF) the panel piezo from sounding when alarms or faults occur. A setting of ON is overridden if
LOCAL CONTROL is set to NO. Default: ON
DISPLAY ADDRESS: Press this soft key to toggle between YES and NO. Choose YES to display
all point address information at the top of event screens and in printouts. Choose NO to suppress
address information display and printing. Default: YES
REMINDER MENU: Press this soft key to bring up the Reminder Menu screen.
ACCEPT: Press this soft key to save the information entered on this screen.
MORE: Press this key to progress to the second Panel Settings screen.
NOTE: A setting of NO (disable) will disable key switch operation.
NOTE: ACS devices programmed for acknowledge, signal silence, and system reset are not affected by
this setting: these commands will still function at the devices if LOCAL CONTROL is set to NO.