AFP-3030 Programming Manual — P/N DOC-01-032:A 26/06/2015 31
Panel Program PrealarmProgram
Figure 3.17 Panel Timers (Menu 2) Screen
Soft Keys
OUTPUT DELAY TIME: Press to enter a value of 00:00 (OFF) or a value of 0:01 to 10:00
minutes (in the format MM:SS, where MM = minutes, SS = seconds). This feature initially causes
alarm signals to sound only in specific areas, monitored by qualified personnel. This allows delay
of the alarm for up to 10 minutes after the start of alarm processing. Refer to
Appendix B, “Special
Zone Outputs” for further explanation of this option. Default: 1:00
DEFAULT TIMERS: Press this soft key to activate default settings for the following:
. ACCEPT: Press this soft key to save the information entered on this screen and return to the
previous screen.
3.2.7 LCD Programming
The LCD Programming screen allows the user to vary the contrast of the display and turn the
backlight on or off.
Program setting for: Default:
Verify Time 30 seconds
Max. Verify 0
Silence Inhibit 0 (disabled)
Auto Silence Off
Verify = Prealarm No
Output Delay Time 1 minute
Table 3.2 Default Timers