72 AFP-3030 Programming Manual — P/N DOC-01-032:A 26/06/2015
PrealarmProgram Autoprogram Menu
3.6.3 Confirmation Screens
SLC Statistics
When autoprogramming is complete, the panel will display a list of the number of modules and
detectors found on each SLC. Refer to
Figure 3.60 for an example of the screen.
Figure 3.60 Autoprogram Confirmation Screen (SLCs)
Soft Keys
REVIEW: Press this soft key to review the new devices found (with the option of adding them to
the program one by one), devices that are in the database that the autoprogram did not find, devices
that have data base and autoprogram information that differs, and devices that are incorrectly
doubled up on a single address. Devices will display in the following order:
• L01M001 through L01M159
• L01D001 through L01D159
• L02M001 through L02M159, etc.
Depending on what information was found, different screens may appear for different points. Refer
to
Figure 3.61 through Figure 3.64 for examples of the screens.
ACCEPT ALL: Press to accept all the new devices that have been found by the autoprogram.
Errors and discrepancies will still be displayed the same as if the REVIEW soft key had been
pressed: however, new devices will not individually display for review and acceptance.