EasyManuals Logo
Home>Notifier>Control Panel>AFP-3030

Notifier AFP-3030 Programming Manual

Notifier AFP-3030
168 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #13 background imageLoading...
Page #13 background image
AFP-3030 Programming Manual — P/N DOC-01-032:A 26/06/2015 7
Section 2: Main Menu and Event Counts Screen
2.1 The Main Menu
The Main Menu screen is the means by which the programmer can access displays, history
information, printing and programming menus. This screen is accessible from the System Normal
Screen, and from most other screens by pressing the ESC/MAIN MENU key.
Figure 2.1 Main Menu Screen
Soft Keys
Pressing the soft keys brings the user to the screens described below.
2.1.1 PSI Status
Pressing the PSI STATUS button will display the status of the local power supply. This informa-
tion includes the supply voltage, battery voltage, PSI output voltage, which supply source the panel
is running from (PSI or battery), whether a battery test is in progress and whether or not the battery
test and charger have been disabled.
Figure 2.2 PSI Status Screen
LAKEVIEW GENERAL HOSPITAL
SYSTEM NORMAL
11:58:45A TUE DEC 23, 2014
PSI STATUS READ STATUS
DISABLE/ENABLE PROGRAM/ALTER STATUS
TEST
HISTORY EVENT/GRAPHIC SCREEN
PSI STATUS
PSU VOLTAGE: 27.3V
BATTERY VOLTAGE: 24.2V
PSI CONTROL STATUS:
PANEL RUNNING FROM PSI SUPPLY
START BATTERY TEST BACK

Table of Contents

Other manuals for Notifier AFP-3030

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier AFP-3030 and is the answer not in the manual?

Notifier AFP-3030 Specifications

General IconGeneral
BrandNotifier
ModelAFP-3030
CategoryControl Panel
LanguageEnglish

Related product manuals