INTELLIGENT PDU USER MANUAL
59
Note: An IP address configured to 0.0.0.0 will act as a wildcard and all requests
will be acted upon.
Read Community: the read-only community string to allow an SNMP V1/V2c
manager to read a SNMMP object.
Write Community: the write-only community string to allow an SNMP V1/V2c
manager to write an SNMMP object.
6. Click Enable and Save.
Configuring Users for SNMP v3
1. Access the Web interface and log in.
2. Under SNMP Managers, select SNMP V3.
3. In the SNMP V3 panel, select the SNMP V3 manager to configure. Select the
pencil icon in the last column.
Figure 48: SNMP V3 Manager
4. The Edit panel pop-up displaying the configurable options.