Building Technologies Division User Manual LMS14... CC1U7471en
6 The settings in detail 07.05.2014
6.5.7 ECO function
Line no. Operating line
HC1 HC2 HC3
730 1030 1330 Summer/winter heating limit
The summer/winter heating limit is used to switch the heating on and off in the course
of the year, depending on the outside temperature. In Automatic operation, switching
on/off takes place automatically, so there is no need for the user to do this manually.
The respective periods of time are shortened or extended by changing the setting.
The Summer/winter changeover function switches the heating off when the attenuated
outside temperature exceeds the adjusted changeover temperature.
The heating switches back on when the attenuated outside temperature drops below
the set value minus 1 K.
The required changeover temperature can be parameterized. The function can be
activated/deactivated.
Increase: Winter operation will start earlier.
Summer operation will start later.
Decrease: Winter operation will start later.
Summer operation will start earlier.
Note!
The function is not active in Comfort mode
The display shows ECO
To give consideration to the building's thermal dynamics, the outside temperature
is attenuated
Example:
°C
730 / 1030 / 1330
730 / 1030 / 1330 -1 K
Figure 19: ECO function – summer/winter heating limit
Key
Line no. Meaning
HC1 HC2 HC3
730 1030 1330 SWHG Summer/winter heating limit
8703 TAged Attenuated outside temperature
t Days
T Temperature
Summer/winter
heating limit