Building Technologies Division User Manual LMS14... CC1U7471en
6 The settings in detail 07.05.2014
6.7.3 Holiday program
If the holiday program is active with all heating circuits (Automatic operation and holiday
program active), the DHW setpoint is set to the Frost protection level and the circulating
pump is deactivated. At the end of the holiday period, the operating level according to
the release applies again. While the holiday program is active, DHW heating can be
triggered at any time by making a manual DHW push (one-time DHW charging to the
Nominal setpoint).
Note!
If the Legionella function was not effected because of a holiday period, it will be
performed the next time DHW is heated to the Nominal setpoint.