EasyManuals Logo
Home>Siemens>Control Unit>LMS14

Siemens LMS14 User Manual

Siemens LMS14
617 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #185 background imageLoading...
Page #185 background image
185/617
Building Technologies Division User Manual LMS14... CC1U7471en
6 The settings in detail 07.05.2014
6.7.5 Priority
Line no. Operating line
1630 Charging priority
Absolute
Shifting
None
MC shifting, PC absolute
When both space heating and DHW heating call for heat, the DHW priority function
ensures that while DHW charging is in progress, the boiler’s capacity is used primarily
for DHW heating.
Note!
On applications with diverting valves, the function is automatically deactivated.
Absolute
Mixing and pump heating circuits stay locked until DHW heating is completed.
Shifting
If the capacity of the heat source is not sufficient, the mixing and pump heating circuits
will be restricted until the DHW is heated up.
None
DHW heating and space heating take place at the same time. In the case of tightly
sized boilers and mixing heating circuits, the DHW setpoint may not be reached if
space heating calls for considerable amounts of heat.
MC shifting, PC absolute
The pump heating circuits stay locked until the DHW storage tank is heated up. If the
capacity of the heat source is not sufficient, the mixing heating circuits will be restricted
also.
6.7.6 Locking signals
Locking signals are used by the heat source to reduce or prevent heat consumption by
the consumers.
If the locking signal exceeds 50%, the DHW charging pump is deactivated. It will be
activated again when the locking signal drops below the threshold value of 50%.
Also, the heat source can calculate a critical locking signal based on a parameterized
maintained boiler return temperature. The impact on the DHW charging pump is the
same as with locking signal Boiler protection.
6.7.7 Forced signals
If required, the heat source can send forced signals to its consumers. When the heat
source delivers a valid forced signal, the DHW setpoint is set to the Legionella setpoint
and – if the DHW temperature is lower – the charging pump is activated. When the
forced signal becomes invalid, the charging pump is deactivated again and the DHW
setpoint will be reset to the normal setpoint.
Charging priority

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens LMS14 and is the answer not in the manual?

Siemens LMS14 Specifications

General IconGeneral
BrandSiemens
ModelLMS14
CategoryControl Unit
LanguageEnglish

Related product manuals