6.35.9 Repetition counter
In the event of erroneous input signals, the repetition counters can be used to influence
the sequence of phases.
Loss of flame during operation
Per default, repetition counter Flame off during operation is set to infinite (25). If the
fault occurs several times, the burner control does not initiate lockout.
No flame on completion of safety time
If there is no flame on completion of the safety time, further repetitions are possible
before lockout occurs.