Building Technologies Division User Manual LMS14… CC1U7471en
6 The settings in detail 28.01.2015
6.18.14 DHW push
The DHW push can be triggered either manually or automatically. It ensures one-time
DHW charging to the Nominal setpoint.
The manual DHW push is triggered by pressing the DHW operating mode button for at
least 3 seconds.
The DHW push is active until the Nominal DHW setpoint is reached. If, at the time of
the manual push, the Legionella function is due, the push is made until the Legionella
setpoint is reached.
Note!
Once triggered, the push can be aborted by switching the operating mode to ECO or
OFF.
Note!
Manual push is also triggered in Off mode when operating mode changeover is active
via input Hx or LPB, or when all heating circuits are in Holiday mode.