6 The settings in detail 28.01.2015
6.17.4 Recooling
Line no. Operating line
4755 Recooling temp
2 functions are available for recooling the buffer storage tank down to the recooling
temperature.
Line no. Operating line
4756 Recooling DHW/HCs
Off
On
Heating energy can be drawn off either by space heating or the DHW storage tank. This
can be selected separately for each heating circuit (operating page for heating circuit
1…).
Off
Function is deactivated.
On
Function is activated.
Line no. Operating line
4757 Recooling collector
Off
Summer
Always
When the collector is cold, heat can be released to the environment via the collector’s
surfaces.
Off
Recooling via the collector is deactivated.
Summer
Recooling via the collector is permitted in summer only.
Summertime is when, at midnight, all available heating circuits switch to summer
operation according to the summer/winter heating limit.
Always
Recooling via the collector is activated throughout the year.
6.17.5 Plant hydraulics
Line no. Operating line
4783 With solar integration
No
Yes
Select here whether the buffer storage tank can be charged by solar energy.
Recooling temp
Recooling DHW/HCs
Recooling collector
With solar integration